Fire Extinguisher Servicing Requirements: BS 5306-3 Explained

3 July 2026 · 6 min read
Close-up of a red fire extinguisher with a pressure gauge and a plain service tag
Key takeaways
  • Article 17 of the Fire Safety Order requires fire-fighting equipment to be maintained in an efficient state, in working order and in good repair.
  • BS 5306-3 is the recognised standard: a basic service every 12 months by a competent person, an extended service at 5 years for water, foam and powder, and at 10 years for CO2.
  • Monthly visual checks can be done in-house; the annual and extended services should be done by a competent engineer and recorded.
  • Third-party certification, such as BAFE SP101, is the simplest way to evidence competence.

Fire extinguishers sit on walls for years looking fine, which is exactly the problem. Pressure leaks, seals perish, powder compacts and nobody notices until the one time it matters. The law requires the equipment to be maintained in efficient working order, and British Standard BS 5306-3 is the recognised way of doing that. Here is what servicing actually requires.

The legal duty

Article 17 of the Fire Safety Order requires the responsible person to ensure that the premises and any facilities, equipment and devices provided for fire safety are subject to a suitable system of maintenance and kept in an efficient state, in efficient working order and in good repair. Extinguishers are the most visible example. The Order does not name a standard; BS 5306-3 is what the fire service, insurers and the industry treat as the benchmark.

General information, not legal advice.

The annual basic service

Every portable extinguisher should have a basic service at intervals not exceeding 12 months, by a competent person. The engineer checks the extinguisher is the right type and correctly sited, examines the body, hose, horn and safety pin, checks the pressure gauge or weighs the cylinder, checks the operating mechanism, confirms the contents are within date, and records the service on the extinguisher label and in your records. Any unit that fails is replaced or taken out of service.

Extended service at 5 and 10 years

Beyond the annual check, BS 5306-3 calls for an extended service: for water, foam and powder extinguishers, every 5 years, which involves discharging, inspecting internally and refilling or replacing; for CO2 extinguishers, every 10 years, which typically means pressure testing or replacement. Many businesses find replacement cheaper than extended service on smaller units. Our guide to how long extinguishers last covers the choice.

Get extinguisher servicing quotes

Match with competent fire equipment engineers for annual servicing and supply. No-obligation quotes.

Monthly checks you can do yourself

Between services, a responsible person can carry out a simple monthly visual check: the extinguisher is in place, unobstructed and visible, the pin and tamper seal are intact, the gauge reads in the green, there is no obvious damage, and the service label is current. Record the check. Our monthly checklist sets it out.

Who can service extinguishers

The standard requires a competent person: someone with the training, tools and knowledge to service to BS 5306-3. In practice that means a trained fire equipment engineer, ideally working for a company third-party certified under the BAFE SP101 scheme. Certification gives you evidence that the service was done properly, which is what you need after an incident.

The records to keep

Keep a fire log that records each service, the engineer and company, what was done and any units replaced, alongside your Fire Risk Assessment and monthly checks. The service label on each extinguisher should show the last service date. Insurers and fire service auditors ask for exactly this.

Sources & further reading

External links open in a new tab. ComSurv is a matching service, not a firm of surveyors, and is not affiliated with these organisations. This article is general information, not legal, surveying or valuation advice; take advice on your specific situation.

Frequently asked questions

How often do fire extinguishers need servicing?+
Annually, by a competent person, in line with BS 5306-3, with an extended service at 5 years for water, foam and powder and at 10 years for CO2. Monthly visual checks can be done in-house.
Is fire extinguisher servicing a legal requirement?+
The Fire Safety Order requires fire-fighting equipment to be maintained in efficient working order. Annual servicing to BS 5306-3 is the recognised way of meeting that duty.
Who can service a fire extinguisher?+
A competent person, which in practice means a trained fire equipment engineer. BAFE SP101 certification is the easiest way to evidence competence.
What records do I need to keep?+
A fire log recording each service, the engineer, the work done and any replacements, plus your monthly in-house checks. Each extinguisher should carry a current service label.